Aluminium Conductors
Manufacturers and exporters of aluminium conductors like
all aluminium conductors, alluminium conductors steel reinforced, all
aluminium alloy conductors, etc.

All
Aluminium Conductors (AAC)
|
IS: 398 (Part I)
| Code |
Nominal Aluminium
Area mm² |
Stranding &
Wire Diameter mm |
Approx Over all
Dia mm |
Approx Mass Kg/Km |
Calculated
Resistance at 20 C Max / KM |
Approx Calculated
Breaking Load KN |
Approx. Calculated
Breaking Load (kN) |
| Gnat |
25 |
7/2.21 |
6.63 |
74 |
1.093 |
4.52 |
4.52 |
| Ant |
50 |
7/3.10 |
9.30 |
145 |
0.556 |
8.25 |
8.25 |
| Wasp |
100 |
7/4.39 |
13.17 |
290 |
0.277 |
15.96 |
15.96 |
| Special |
150 |
19/3.18 |
15.90 |
415 |
0.915 |
23.28 |
23.28 |
| Spider |
240 |
19/3.99 |
19.95 |
654 |
0.1244 |
35.74 |
35.74 |
| Butterfly |
300 |
19/4.65 |
23.25 |
888 |
0.01971 |
48.74 |
48.74 |
|
 |
 |
 |
 All
Aluminium Alloy Conductors (AAAC)
Aluminium alloy wires used in the
construction of standard aluminium alloy conductors.
Physical contents of alluminium alloy :-
1. Resistivity - 0.0326 Ohms mm2/m at 20°C
2. Density - 2.70 kgm/dm3 at 20°C
3. Coefficient of Linear Expansion - 23 x 10-6 / °C
4. Constant Mass Temperature Coefficient (a) - 0.00360/ °C
5. Material - Heat treated Al. Mg. Si. Alloy
- Approximately 0.5% Mg & 0.5% Si
- Having Mechanical & Electrical properties as specified in table
above :
|
 |
 |
| Sl. No. |
Nom. Al Area mm |
Standing & wire Dia in mm |
Approx. Overall Dia in mm |
Approx. Mass in kg/km |
Calculated Maximum Resistance at 20 C
(Ohms/km) |
Approx. Calculated Breaking Load (kN) |
| 1 |
15 |
3/2.5 |
5.39 |
40.15 |
2.3040 |
4.33 |
| 2 |
22 |
7/2.00 |
6.00 |
60.16 |
1.5410 |
6.45 |
| 3 |
34 |
7/2.50 |
7.50 |
94.00 |
0.9900 |
10.11 |
| 4 |
55 |
7/3.15 |
9.45 |
149.20 |
0.6210 |
16.30 |
| 5 |
80 |
7/3.81 |
11.43 |
218.26 |
0.4250 |
23.41 |
| 6 |
100 |
7/4.26 |
12.78 |
272.86 |
0.3390 |
29.26 |
| 7 |
125 |
19/2.89 |
14.45 |
342.51 |
0.2735 |
36.64 |
| 8 |
148 |
19/3.15 |
15.75 |
406.91 |
0.2298 |
43.50 |
| 9 |
173 |
19/3.40 |
17.00 |
474.02 |
0.1969 |
50.54 |
| 10 |
200 |
19/3.66 |
18.30 |
549.40 |
0.1710 |
58.66 |
| 11 |
232 |
19/3.94 |
19.70 |
636.67 |
0.1471 |
68.05 |
| 12 |
288 |
37/3.15 |
22.05 |
794.05 |
0.1182 |
84.71 |
| 13 |
346 |
37/3.45 |
24.15 |
952.56 |
0.0984 |
101.58 |
| 14 |
400 |
37/3.71 |
25.97 |
1101.63 |
0.0855 |
117.40 |
| 15 |
465 |
37/4.00 |
28.00 |
1280.50 |
0.0734 |
136.38 |
| 16 |
525 |
61/3.31 |
29.79 |
1448.39 |
0.0651 |
146.03 |
| 17 |
570 |
61/3.45 |
31.05 |
1573.71 |
0.0598 |
158.66 |
| 18 |
604 |
61/3.55 |
31.95 |
1666.00 |
0.0568 |
167.99 |
| 19 |
642 |
61.3.66 |
32.94 |
1771.36 |
0.0534 |
178.43 |
| 20 |
695 |
61/3.81 |
34.29 |
1919.13 |
0.0492 |
193.25 |
| 21 |
767 |
61/4.00 |
36.00 |
2115.54 |
0.0446 |
213.01 |
 |
 |

Aluminium
Conductors Steel Reinforced (ACSR)
ACSR
Code
Word |
Cond.
Area mm2 |
Stranding&
Wire Dia in mm |
Calculated
sectional Area Sq.mm |
Approx overall Dia
mm |
Weight
kg/km |
Calc.
Electrical Resistance at 20oC Ohms/km |
Approx
Calc.
Breaking Load(KN) |
| Alum. |
Steel |
Alum. |
ACSR |
ACSR |
ACSR |
Alum. |
Steel |
Cond. |
Cond. |
| MOLE |
10 |
6/1.50 |
1/1.50 |
10.60 |
12.37 |
4.50 |
43 |
29 |
14 |
2.780 |
3.97 |
| SPECIAL |
18 |
6/1.95 |
1/1.95 |
18.10 |
21.12 |
5.88 |
73 |
50 |
23 |
1.618 |
6.74 |
| SQUIRREL |
20 |
6/2.11 |
1/2.11 |
20.98 |
24.48 |
6.33 |
85 |
58 |
27 |
1.394 |
70.61 |
| WEASEL |
30 |
6/2.59 |
1/2.59 |
31.61 |
36.88 |
7.77 |
128 |
87 |
41 |
0.929 |
11.12 |
| RABBIT |
50 |
6/3.35 |
1/3.35 |
52.88 |
61.70 |
10.05 |
214 |
145 |
69 |
0.552 |
18.25 |
| RACCOON |
80 |
6/4.09 |
1/4.09 |
78.83 |
91.97 |
12.27 |
319 |
216 |
103 |
0.371 |
26.91 |
| DOG |
100 |
6/4.72 |
7/1.57 |
105.00 |
118.50 |
14.15 |
394 |
288 |
106 |
0.279 |
32.41 |
| WOLF |
150 |
30/2.59 |
7/2.59 |
158.10 |
194.90 |
18.13 |
726 |
437 |
289 |
0.187 |
67.34 |
| PANTHER |
200 |
30/3.0 |
7/3.00 |
212.10 |
261.50 |
21.00 |
974 |
586 |
388 |
0.139 |
89.67 |
| KUNDAH |
400 |
42/3.50 |
7/1.96 |
404.10 |
425.20 |
26.88 |
1281 |
1116 |
165 |
0.073 |
88.79 |
| ZEBRA |
420 |
54/3.18 |
7/3.18 |
428.90 |
484.50 |
28.62 |
1621 |
1186 |
435 |
0.069 |
130.32 |
| MOOSE |
520 |
54/3.53 |
7/3.53 |
528.50 |
597.00 |
31.77 |
2004 |
1461 |
537 |
0.056 |
161.20 |
| MORKULLA |
560 |
42/4.13 |
7/2.30 |
562.70 |
591.70 |
31.68 |
1787 |
1553 |
228 |
0.052 |
120.16 |
 |
 |
Lay Ratio for AAC/ACSR /AAAC
No. of
Wires
in conductors |
6 Wire
Layer |
12
Wire Layer |
18
Wire Layer |
24
Wire Layer |
| Min |
Max |
Min |
Max |
Min |
Max Steel |
Min |
Max |
| 7 |
10 |
14 |
- |
- |
- |
- |
- |
- |
| 19 |
10 |
16 |
10 |
14 |
- |
- |
- |
- |
| 37 |
10 |
17 |
10 |
16 |
10 |
14 |
- |
- |
| 61 |
10 |
17 |
10 |
16 |
10 |
15 |
10 |
14 |
|
 |
Turnkey Projects

Overhead
Lines, Sub Station and PLCC
We are one of the pioneer manufacturer of
AAC/ACSR/Alloy overhead Conductors & AB Cables in India and we are also
doing Trunkey Projects of different electricity boards which includes
erection of overhead lines upto 440 KV, establishment of new sub stations,
rennovations and amalgation of of old sub stations upto 220 KV, powerline
carrier communication lines at different sub stations, etc.
Our overhead lines are strictly in compliance with international standards
of quality, reliability and efficacy. Made from superior quality materials,
these cables minimize power loss and ensure higher performance. Recognizing
our quality products, we have been awarded with INR 350 crores worths of
orders from different electricity boards under Asian Development Bank (ADB)
loan, Rural Electrification (REC) and Rajeev Gandhi Yojna.